Combination of contactors Eaton DIUL

Add to selection
General information
Ordercode YESSS
0509-1975
Product code
278233
EAN code
4015082782337
Product group
Combination of contactors
Brand
Eaton
Serie
DIUL
Type
DIULM50/11(110V50HZ,120V60HZ)
Wendeschützkombination, 380 V 400 V: 22 kW, 110 V 50 Wendeschützkombination, 380 V 400 V: 22 kW, 110 V 50 Hz, 120 V 60 Hz, Wechselstrombetätigung
Product description

Reversing contactor combination, Application: Contactor combinations for starting motors with two directions of rotation, Accessories: DIUL reversing combinations, Utilization category: NAC-3: Normal AC induction motors: starting, switch off during running, AC-4: Normal AC induction motors: starting, plugging, reversing, inching, Rated operational current AC-3 380 V 400 V: Ie= 50 A, Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V: P= 15.5 kW, 380 V 400 V: P= 22 kW, 660 V 690 V: P= 30 kW, Actuating voltage: 110 V 50 Hz, 120 V 60 Hz, Voltage AC/DC: AC operation, Notes: Also suitable for motors with efficiency class IE3. , IE3-ready devices are identified by the logo on their packaging.

Product specifications
Function
Reversing contactor
Rated control supply voltage at AC 50 Hz
110 - 110 V
Voltage type for actuating
AC
Rated operation power at AC-3, 400 V
22 kW
Rated operation current Ie at AC-3, 400 V
50 A
Rated control supply voltage at AC 60 Hz
120 - 120 V
Rated control supply voltage at DC
0 - 0 V
Rated operation power NEMA
29.8 kW
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP)
IP00
Degree of protection (NEMA)
Other
Rated operation current Ie at AC-1, 400 V
50 A
Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
6
Type of electrical connection for auxiliary- and control current circuit
Screw connection
Rail mounting possible
No
Voltage type (operating voltage)
AC
Operating voltage at AC 50 Hz
230 - 690 V
Operating voltage at AC 60 Hz
230 - 690 V
Operating voltage at DC
0 - 0 V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
2
Number of auxiliary contacts as change-over contact
0
Width
110 mm
Height
115 mm
Depth
147 mm
more specifications
^